Skip to main content

Safety blow-off valve PLUS

This valve has a dual function. In addition to the safety blow-off valve function, it contains an electrical contact. It switches before the blow-off valve opens and warns of a future alarm. This allows the maintenance service to eliminate the cause of the fault before an alarm situation arises.

Features & advantages

  • Protection against overpressure in the vacuum system
  • Electrical signal before a gas alarm is triggered
  • Response pressure of the blow-off valve approx. 30 mbar
  • Response pressure of the contact sensor approx. 15 mbar
  • Materials in media contact PVC, PVDF, FPM
  • Delivery incl. wall bracket