Safety Shutoff Valves
 
 

Safety Shutoff Valves

Double safety for vacuum lines

Contact a broken vacuum line and a leaky vacuum regulator on simultaneously, uncontrolled escape of chlorine gas. The safety shutoff valve prevents this from happening, ensuring the highest possible level of safety. The shutoff valve also prevents water penetration into the vacuum controller if the injector check valve is leaky.

 

Safety Shutoff Valves

 
  • Lock the vacuum line upon insufficient vacuum
  • Protect the vacuum regulator against water from the injector

Further product views

 
 
 
 
 
Chlorine gas flow rateHose connection 8/12 mmkg/h 5
Hose connection 12/16 mmkg/h 15
PVC threaded connection DN12 / Ø 16 mmkg/h 15
Response vacuummbar - 50
Permitted operating pressureInput sidebar 8
Output sidebar 4
Nominal width DN12
Material in contact with the media PVC, PVDF, Hastelloy, FPM
Weightg 1200 approx.

Subject to technical changes

   
 
 

BA: Operation instruction
PI: Product information

     
 
 
835