Description:
Dosing chlorine gas in larger amounts To avoid the risk of chlorine leakage all pipings and devices downstream of the vacuum regulator are below atmospheric pressure. In case of leakage air is sucked into the system, but no chlorine escapes into the atmosphere.
Features & advantages:
- Flow rate with chlorine gas: up to 200 kg/h
- Safe operation with vacuum technology
- Included relief valve
- Highly resistant materials
- Optional pressure gauge
Flow rate with chlorine | kg/h | up to 200 | ||
---|---|---|---|---|
Inlet pressure | bar | 1.5...16 | ||
Operation vaccum | mbar | -50 | ||
Relief pressure | mbar | 500 | ||
Pressure gauge (optional) | bar / mm | 0...16 / Ø63 | ||
Materials of construction | Inlet valve | Nickel plated brass, ceramic, Hastelloy | ||
Vacuum part | PVC | |||
Sealings | FPM, PTFE | |||
Weight (with flange and pressure gauge) | kg | 8 | ||
Ambient temperature | °C | 0...40 (no direct sun light) |
Description | Order no. | ||
---|---|---|---|
Flange DN 25 / PN 40 with tongue acc. EN1092 shape C | Threaded flange 1" NPT female | 15927 | |
Weld neck flange Ø33.7 x 4 mm | 39516 | ||
Liquid sealing compound 50 ml for bonding of 1” NPT-threads | |||
Ammonia solution 50 ml for leakage test | 13514 | ||
8/12 mm PE tubing for relief valve | 97124 |
Description | Order no. | |
---|---|---|
Small maintenance kit (for annual service) gaskets, valve seat, screws, flange gasket, rubber hose for relief valve | 39511 | |
Large maintenance kit (after 3 years) includes small maintenance kit, diaphragm, valve cone, spring | 39512 | |
Maintenance kit for diaphragm disc: Diaphragm, screws, rubber hose for relief valve (included in the large maintenance kit) | 39513 | |
Pressure gauge 0...16 bar connection 1/4” NPT male (Replacement is recommended after 5 years of use) | 24087599 |
Downloads
- https://www.lutzjescoamerica.com/fileadmin/data/dokumente/pg2/LJ-Chlorgas_Vakuumregler_C_2700_V-DE-BA.pdf
- https://www.lutzjescoamerica.com/fileadmin/data/dokumente/produktinfos/LJ-C2700_V-DE-PI.pdf
- https://www.lutzjescoamerica.com/fileadmin/data/dokumente/pg2/LJ-Vacuum_regulator_for_chlorine_gas_C_2700_V-EN-BA.pdf
- https://www.lutzjescoamerica.com/fileadmin/data/dokumente/produktinfos/LJ-C2700_V-EN-PI.pdf