Vacuum regulator C 2214
Product number:
20401409
Product information "Vacuum regulator C 2214"
The C 2214 is designed for individual operation. For use on gas drums, a heated droplet separator is optionally available on the pressure side in the inlet valve of the C 2214. A safety blow-off valve is integrated and prevents an impermissible increase in pressure in the downstream vacuum line system. The quantity of gas dosed can be optimally adjusted on the C 2214 using a dosing valve and flow meter.
Features & advantages
- Throughput capacity with chlorine gas: up to 4 kg/h
- Residual pressure protection: Prevents the chlorine cylinder from being completely evacuated to prevent corrosion caused by moisture in the air
- Filter: To protect the valve from dirt particles from the chlorine cylinder or the connection area
- Cylinder pressure gauge: For displaying the pressure in the chlorine tank
- Integrated safety blow-off valve
- Flow meter with manual setting
- Gas filter
- Compact design
- Available with all standard gas connections
| MATCHCODE: | 0204V51N1N0080L1A |
|---|---|
| Functions::: | The Vacuum regulator is used to reduce the gas pressure from the |
| Type: | C 2214 |
| Input::: | Union nut G5/8 - BS 341 |
| Dosing connection: | Hose clamp connection 8/12 |
| Blow-off connection::: | Hose clamp connection 8/12 |
| Flow meter:: | 4 - 80 g/h |
| Medium:: | Chlorine gas |
| Pressure gauge::: | 0 - 16 bar [g] |
| Residual pressure protection::: | 0.1 bar |
| Function-2: | Overpressure of the gas containers to negative pressure [Vacuum]. |
| Function-3: | When the operating vacuum is removed, the inlet valve closes and |
| Function-4: | prevents the flow. |
| Function-5: | Suitable for dry chlorine gas [purity > 99.5%]. |