Technostar 2000
 
 

TECHNOSTAR

Alternative and prize-winning disinfection technology

The generation of hypochlorous acid takes place in an electrolysis cell installed in a bypass of the clean water pipe. It is controlled via an instrumentation and control system with continuous controller output with PI control response from
4 to 20 mA. Each electrolysis cell can be equipped with a temperature sensor for temperature control.

 

TECHNOSTAR

 
  • Swimming pool water that is gentle to the skin
  • No reddened eyes, no irritation of the mucosa
  • No typical chlorine smell in the swimming pool
  • No chlorine chemicals
  • Salt for disinfection
  • Simple installation
  • Disinfection capacity adjustable
  • Low maintenance effort
  • Safe, economical and environmentally friendly

Further product views

 
 
 
 
 
 

Control unit

TECHNOSTAR 2000 ST2000 AX-2502000 AX-2x250
Power supply 230 V, 50 Hz400 V, 50 Hz
Power supply fuseA 1 x 16 3 x 16
Nominal currentA 1,5 / 2,0 / 2,45,82 x 5,8
Nominal powerVA 400 / 500 / 6001.4002.800
Analogue inputmA 4 – 20 mA2x 4 – 20 mA
Digital inputs Temperature monitor, flow-through monitor, external release
Display Graphical display
Control Programmable memory with proportional integral control of electrolysis current at constant voltage
Protection class IP54
Ambient temperature°C 10 – 35
Dimensions
(W x H x D)
mm 600 x 800 x 2501200 x 1200 x 400
Weightkg approx. 60approx. 100
 

Electrolysis cell

ST-80ST-160AX-GAX-F
Number of electrolysis cells 241
Disinfectant capacity at a salt content of ~0,45 %g Cl/h 0 – 80 0 – 160 0 – 250
CurrentA 0 – 12 0 – 200 – 40
Voltage 28 V DC (according to VDE 0100)
Electrical connection Pin terminalsPlug
Cable 4 m, 2 x 6 mm²4 m, 2 x 10 mm²
Temp. of pool water°C 15 – 40
Nominal piping width DN50 / Ø63mmDN100 / Ø110mm
Dimensions (Ø x L) Ø63 x 335 mmØ110 x 555 mm
Connection ThreadFlange
Housing/electrolysis plates material PVC (transparent) / titanium (coated)
Elektrolysis plates package Fixed mountedReplaceable
Weightkg ~2~8
Salt content% > 0,35
Flow speedm/s < 1,5

Subject to technical changes

   
 
 
910