EASYZON D
 
 

EASYZON D

Dosing disinfectant properly

EASYZON D provides a compact system for the on-site production of chlorine dioxide, characterized by reliable functioning and simple operation. The system operates according to the acid-chlorite process in batch mode and uses commercial concentrations of hydrochloric acid and sodium chlorite. Dosing pumps ensure a reliable delivery of the chemicals into the pressure-resistant reactor of the system.

 

EASYZON D

 
  • Disinfecting power stable over a long period of time
  • Production directly on-site
  • Cost-efficient
  • Compact design
  • User-friendly operation
  • Integrated monitoring of all the functions
  • Disinfection works even at high pH values

Further product views

 
 
 
 
 
EASYZON 15 Dd/Compact 30 Dd/Compact 30 Dd/Compact
Max. pressurebar 10
Max. production capacity
at max. pressure
g ClO2/h 14 26 57
Max. production capacity
at 4 bar
g ClO2/h 18 32 72
Type dosing pump MAGDOS LD 2
Chemicals Hydrochloric acid (HCl) 9 % in accordance with EN 939
Sodium chlorite (NaCiO2) 7.5 % in accordance with EN 938
Consumption per chemical for 100 % productionl/h 0.45 0.8 1.8
Minimum flow rate of dilution water
at (max. 2 g Cl02/l)
l/h 9 17 36
Pressure loss waterbar max. 0,2
Concentration in the reactorg ClO2 20
Product concentration after pre-dilutiong ClO2 EASYZON D-B: 0.5 – 2
EASYZON D-D: < 2
Operating voltage 230 V / 50 Hz
Protection class IP54
Power consumptionW 19
Max. current consumption during dosing strokeA 1.1
Weightkg 25 approx.
Ambient temperature°C 5 – 40 (no exposure to direct sunlight)
Temperature of the medium°C 5 – 35
Air humidity% max. 90

Subject to technical changes

 
EASYZON 100 Dd 200 Dd 600 Dd 800 Dd 1400 Dd
Max. pressurebar 10 6 8 5
Max. production capacity
at max. pressure
g ClO2/h 101 239 601 835 1462
Max. Produktionsleistung
at 4 bar
g ClO2/h 115 247 613 844 1478
Type dosing pump MAGDOS LD 4 MAGDOS LD 10 MEMDOS DX 25 MEMDOS DX 50
Chemicals Hydrochloric acid (HCl) 9 % in accordance with EN 939
Sodium chlorite (NaCiO2) 7.5 % in accordance with EN 938
Consumption per chemical
for 100 % production
l/h 2.9 6.2 15.4 21.1 37
Minimum flow rate of dilution water
at (max. 2 g Cl02/l)
l/h 58 124 307 422 739
Pressure loss waterbar max. 0.2
Concentration in the reactorg ClO2 20
Product concentration after pre-dilutiong ClO2 EASYZON D-B: 0,5 – 2
EASYZON D-D: < 2
Operating voltage 230 V / 50 Hz
Protection class IP54
Power consumptionW 25 50 120
Max. current consumption during dosing strokeA 1.4 0.7 1.5
Weightkg 25 approx. 50 approx. 70 approx. 75 approx.
Ambient temperature°C 5 – 40 (no exposure to direct sunlight)
Temperature of the medium°C 5 – 35
Air humidity% max. 90

Subject to technical changes

   
 
     
 
 